Conspec’s CS0352-MP carbon monoxide gas sampling system detects smoldering hot spots in your mill/pulverizer. The dual probe system allows for detection of elevated carbon monoxide levels in separate areas to provide an extra layer of protection against fire situations like “mill puffs”.
The Conspec dual probe gas sampling system identifies smoldering hot spots and helps to mitigate a fire situation. An industry standard 4-20mA analog output, relays, and/or ethernet communications can be easily connected to any existing PLC, DCS, or EMS system. Conspec’s sampling probes feature an auto blow-back function which clears any obstructions reducing costly maintenance and down time. The CS0352-MP also has a maintenance mode for the testing of internal components and deactivates pumps for spray down/deluge. Systems can be customized for your specific needs and Conspec offers commissioning upon final installation of the system.
Maintenance Mode – Allows testing of internal components to verify proper operation.
Low-Flow Detection – Alerts operators if the probe may have obstructions, ensuring accurate readings and system reliability.
Auto Blow-Back – Clears probe obstructions automatically, maintaining sensor performance and minimizing downtime.
Automatic Reset – Restores system operation seamlessly after power loss or interruption, reducing manual intervention.
Pump Control Flexibility – Pumps can be deactivated during spray and/or deluge.
Industry Standard Outputs – Provides widely compatible signals and outputs for integration with external control and alarm systems.
Mechanical
Enclosure: Metallic NEMA 4
Dimensions: 40 in × 30 in × 12 in (1016 mm × 762 mm × 305 mm)
Weight: Approximately 120 lb (54.4 kg)
Mounting: 4 mounting holes with optional mounting feet
Environmental
Operating Temperature: 32°F–120°F (0°C–50°C)
Operating Humidity: 0–100% Condensing
Water removal system to operate in humid conditions
Electrical
Operating Voltage: 120 VAC Input Power
Current Consumption: ~2 A
Output Signals: Linear 4–20 mA / Dry Contact / Ethernet / Fiber Optic
System
Sensor Types: Electrochemical
Keypad: Yes
Turnkey Software Programming: Yes
Display: Allen Bradley PanelView Color Touchscreen
Alarm Set Point #1: Customer Defined
Alarm Set Point #2: Customer Defined
System Test: Allen Bradley Touchscreen Activated
Minimum Air Requirement: 90 psi instrument air, 15–25 scfm