Designed for chemical-laden harsh environments, the Model D390 is the most suitable flame detector for semiconductor cleanrooms and wet benches.
The Model D390 is a stand-alone 3IR fire & flame detector in a totally sealed polypropylene enclosure specifically designed for semiconductor clean rooms and wet benches. The D390 detectors is optimized to respond to fire sources from hydrocarbon and non-hydrocarbon fuels while rejecting non-fire false alarm sources. The D390 detectors requires an external 24 VDC power source and is supplied with Alarm / Auxiliary / Fault relays, 4-20 mA Analog and RS485 Modbus outputs. The flame detector is supplied with an integral 10-foot Teflon Coated multi-conductor cable for wiring to external devices. The detector can store 200 events and 6FireGraphs in its FRAM memory.
Multi-Spectrum Detection – 3IR design detects flame and fire across multiple spectrums for high false alarm immunity.
Event Logging – stores events and 6 FireGraphs for accurate tracking and analysis.
Automatic Self-Test – Checks electronic circuitry and Optical Path Integrity test with OptiRadar®Leak-Proof Polypropylene enclosure.
Easy Installation – Integral cable harness for easy field wiring, and test mode for manual testing.
Made in the USA with a 5-Year Warranty – Built to high standards for long-term reliability.
General
Field-of-View: 90° Field-of-View
Response Time: Alarm: 3-5 Seconds
Spectral Sensitivity: IR: 2-5 microns (3 discrete bands)
Detection Range: 2” Dia. n-Heptane fire, distance 4.5 ft.; 12 x 12” IPA fire, distance 30 ft.
Electrical
Operating Voltage: 24 VDC nominal (18-31), Regulated
Power Consumption: Standby: 60 mA @ 24 VDC; Alarm: 90 mA @ 24 VDC
Visual Indications: Green LED – Normal, Red LED – Alarm, Amber LED – Fault
Communication: RS485 ModBus
Wiring: Integral cable harness 10 ft. long; 20AWG 15 conductor shielded cable
Analog Output: 0-20 mA Stepped – Source
Relays Outputs: Alarm, Auxiliary & Fault; SPDT—contacts rated 2A @ 24 VDC; Alarm/Aux. relays: De-Energized; Fault relay: Energized when powered
Mechanical
Enclosure Material: Molded Polypropylene
Environmental
Temperature Range: -40 to +158°F (-40 to +70°C)
Humidity Range: 5 to 95% relative humidity, non-condensing
Enclosure Type: NEMA 4 & 4X, IP67, watertight, dust-tight
Semiconductor Clean Rooms
Wet Bench Working Area
Wet Bench Plenum
Semiconductor Processing Facilities
Equipment Behind Wet Bench Area
Under-Floor Area of Clean Rooms
RFI & EMC compliant
Meets SIL 2 requirements
D390-111-K11: Detector with sealed Polypropylene enclosure, Kal-Rez O-Ring, Relays & 4-20 mA outputs, and 10-ft. cable.
DA-004: Polypropylene bracket mounting assembly