Primusâ„¢ V

COMMERCIAL LIFE SAFETY NETWORK CONTROLLER

The Primus V commercial network controller combines gas, heat, and flame detection measurements into a single, coordinated life-safety system. Designed for commercial applications where multiple hazards may be present, the Primus V unifies diverse sensor inputs and translates them into actionable intelligence.

With native BACnet and Modbus capability, the Primus V seamlessly communicates with any facility’s BMS / BAS, enabling real-time coordination between detection, ventilation, alarms, and facility controls. Using Subcon software (sold separately), operators can configure, monitor, and manage all connected devices from a single interface; eliminating complexity while providing a comprehensive, system-wide view of safety conditions.

The Primus V is more than just a controller; it’s an integrated platform that transforms individual detection points into a cohesive, responsive safety ecosystem.

PRODUCT FEATURES
Remote I/O Control Allows operators to remotely manage inputs and outputs for every connected Optio-based monitor.
High-Capacity Sensor Support Accommodates up to 6 sensors per monitor, enabling a single Primus V controller to manage a network of up to 576 total sensors from a single location.
Six Integrated Relay Outputs Includes 6 × 2 A @ 24 VDC, 0.5 A @ 120 VAC Normally Open/Normally Closed relays with optional failsafe mode for reliable alarm and control activation.
Local & Remote 4–20 mA Outputs Offers two local analog outputs plus twelve Modbus-driven remote 4–20 mA outputs for flexible integration.
Strobe & Horn Output Provides a direct output port for local audible and visual alarm devices.
Time-Stamped Data Logging Records all state changes and alarm events with accurate time stamps for compliance and diagnostics.
Configurable Multi-Zone Operation Supports up to 12 unique zones to separate alarm logic and control functions across your facility.
Flexible Communication Options Integrates with building automation systems and building management systems (BAS / BMS) via BACnet, Modbus RTU, analog 4–20 mA, and relay outputs.
Electrical
Operating Voltage 16–24 VAC, 12–24 VDC
Current Consumption 100 mA typical, 2.5 A max
Mechanical
Enclosure NEMA 4
Dimensions 9 × 9 × 5.7 in (230 × 230 × 145 mm)
Weight 5.5 lb (2.47 kg)
Mounting Various options
Environmental
Operating Temperature -4°F to +122°F (-20°C to +50°C)
Operating Humidity 0-95% RH non-condensing
Communication
Supported Protocols Modbus RTU, Modbus TCP, Wi-Fi
Pending Protocols BACnet IP
I/O Capabilities
Relay Outputs 6 × SPDT 2 A @ 30 VDC
Local Analog Outputs 2 × 4–20 mA
Remote Modbus Analog Outputs 12 × 4–20 mA
Alarms
Onboard Buzzer 72 dBA @ 3 ft (0.9 m)
External Horn/Strobe 97 dBA @ 3 ft (0.9 m)
Trouble Alarm Sensor failure (high / low), communication error, or internal fault.
Custom Alarms 4 levels with off delay timers
User Interface
Control Options 4 local tactile buttons, or remote via Conspec Subcon Windows software
Horn Silence 1 local horn silence button
PC Connection Built-in RS232 port
(for configuration purposes only)
Scan ports 3 × RS485
Zoning
Programmable Zones Up to 12 programmable zones
Nemko UL61010-1
UL 2075 (pending)
City of LA Approval

Request Primus V Pricing / Availability

Looking for dependable gas detection and control solutions at the right price, without the long wait? Conspec offers industry-leading turnaround times and competitive pricing on all of our safety solutions. Please share some information about your project and a member of our team will respond at their earliest convenience.