Maximum sound pressure level output of 115dB(A)
Automatic synchronisation on multi-beacon & sounder systems
UL464 / CAN/ULC-S525 & UL1638 / CAN/ULC-S526
Nominal Voltage: Voltage range: Xenon Strobe Nominal current: Alarm Horn Nominal current: Combined Nominal current: Combined Max. current:
24Vdc 20-28Vdc 323mA 185mA 508mA 555mA
115Vac 110-120Vac 50/60Hz 129mA 73mA 200mA 264mA
230Vac 220-240Vac 50/60Hz 79mA 48mA 127mA 149mA
Part Code: Identifier: Description:
Product type: D1xC1X05 Combined Alarm Horn & Xenon Strobe
Horn type: F Flare re-entrant horn
Voltage: DC024 AC115 AC230 20-28V dc 110-120Vac 220-240Vac
Cable entries:[e] A B C D E Note: 1×1/2″NPT, 2xM20 1×1/2″NPT, 2×1/2″NPT-adaptors 1×1/2″NPT, 2×3/4″NPT-adaptors 1×1/2″NPT, 1 x M20, 1×1/2″NPT-adaptor 1×1/2″NPT, 1 x M20, 1×3/4″NPT-adaptor All entries, excluding thread adaptors, supplied with stopping plugs installed.
Stopping plug/ adaptor material: [m] B N S Brass Nickel Plated Stainless Steel
Bracket/Guard material: [s] 1 3 A4 316 Stainless Steel A4 316 St/St with Equip. Tag
Product version: [v] A D UL, cUL, ULC, IECEx, ATEX, PESO, CSFM Class II – UL, cUL
Product option: [o] 1 Z T X Y Standard product Custom alarm tone software – contact E2S Tropicalisation Custom configuration – contact E2S Stage control Config. 4
Enclosure colour: [x] G R Grey Red
Lens colour: [y] A B C G M R Y Amber Blue Clear Green Magenta Red Yellow
Accessories:
SP65-0001-A4 SP65-0003-A4 Pole Mount Bracket Kit 2″ St/St A4 (316) Sunshade – St/St A4 (316)
UL/cUL/ULC File ref: E230764
IECEx Certificate: IECEx ULD 19.0008X
ATEX Certificate: DEMKO 19 ATEX 2141X
CSFM listing: 7136-2279:0506
UKCA certificate: UL21UKEX2132X
NEC Class / Zone Class I Zone 1 IIC T4 Gb Ta -55°C to +85°C Class I Zone 1 IIC T4A Gb Ta -55°C to +80°C Class I Zone 1 IIC T5 Gb Ta -55°C to +60°C Class I Zone 1 IIC T6 Gb Ta -55°C to +45°C
CEC Class / Zone Class I Zone 1 IIC T5 Gb Ta -55°C to +55°C Class I Zone 1 IIC T6 Gb Ta -55°C to +45°C
NEC / CEC Class / Div Class I Div 1 ABCD T5 Ta -55°C to +55°C Class I Div 1 ABCD T6 Ta -55°C to +45°C
IECEx / ATEX II 2G Ex db IIC T4 Gb Ta -55°C to +75°C II 2G Ex db IIC T5 Gb Ta -55°C to +55°C II 2G Ex db IIC T6 Gb Ta -55°C to +40°C (DC only) II 2D Ex tb IIIC T115°C Db Ta ‐55°C to +75°C
NEC Class / Zone – Product version: D Class II Zone 20 IIIB T4A Gb Ta -55°C to +70°C Class II Zone 20 IIIB T5 Gb Ta -55°C to +60°C Class II Zone 20 IIIB T6 Gb Ta -55°C to +45°C
NEC Class / Div – Product version: D Class II Div 1 Group FG T4A Ta -55°C to +70°C Class II Div 1 Group FG T5 Ta -55°C to +60°C Class II Div 1 Group FG T6 Ta -55°C to +45°C Class III Div 1 Ta -55°C to +70°C See product manual for full voltage specific coding.